The Air Flow Sensor is also known as a hygrometer, that is used to measure humidity present in the air. Generally, both the humidity sensor & temperature sensor are used to detect humidity. Humidity is defined as the amount of moisture or water content present in the air. This water is present in gaseous form in the air. A less humid air indicates that the air is dry, which generally happens for dry areas. And high humidity means a lot of water is present in the air, which is the general case in coastal areas.
Series/ Model | AFMB |
---|---|
Medium | Air |
Length | 100~3000mm |
Accuracy | < 3% (related with the install position, quantity of blades installed and the matched DP transmitter) |
Repeatability | < 0.3% |
Operating temperature | up to 85°C |
Max pressure | 1 bar (static pressure) |
Approval | CE |
Series/ Model | AVT |
---|---|
Medium | Air |
Range | 0~5/10/15/20m/s or 0~16/32/48/64ft/s |
Accuracy | m/s: ± (0.2m/s+5% reading) or ± (0.2m/s+3% reading) @0.5~20m/s; ft/s: ± (0.65ft/s +5% reading) or ± (0.65ft/s +3% reading) @1.6~64ft/s 25°C, 55%RH, 1013hPa |
Response time | typical 2s |
Output | 4~20mA (3 wires), 0~10/0~5VDC, RS485/Modbus |
Display | LCD, with unit m/s or ft/s, DIP switch selectable |
Approval | CE |
Series/ Model | AVTP |
---|---|
Medium | Air |
Probe Length | 150 mm & 210 mm |
Range | 0~30m/s |
Accuracy | ±(0.03m/s+5%) , ±(0.2m/s+3%) |
Temperature compensation | 10~40°C |
Output |
4-20mA/ 0- 10Vdc/ RS485 modbus |
Response time | typical 2s |
Approval | CE |